FB150
Capacity & Ranges
Manufactured from Stainless Steel the Flueboost 150 will handle flue gases up to 200°C with heat outputs up to 150,000 Btu/h (44Kw). If fitting to a gas fire consult the fire manufacturer first.
Time Delay
The fan has a built in pre-purge (time delay) of approximately 30 seconds, this is to purge the boiler of any gases before ignition.
Pressure Switch
The pressure switch has contacts which close with air flow and open in the event of a fan failure. The presure switch has an interlock installed which ensures a fail safe operation.
Connections
Two plug-in electrical connectors are supplied, a three pin socket for the power supply and a two pin plug for the output supply. The output supply is 220/240 volt switch live.
Electrical & Sound Details
220/240 Volt Single Phase 65 Watt
Starting Current 1.2Amp
Running Current 0.19Amp
Sound Level 56dba @ 3 Metres
Weight 3.6Kg
Shipping
This item is shipped direct from the manufacturer.